These affected batteries formed a new battery module with higher voltage, which overcharged the batteries in Zone 6. Thus, the second TR source was created in the zone far from the heaters. The series of TR phenomena, as described above, is the mechanism of thermal runaway discrete propagation ( Fig. 7 b).